Address, baud rate, parity, protocol: Some Instruments can communicate with different protocols, e.g. Modbus RTU or Modbus ASCII or some ANSI protocol. Check that the instrument is setup correctly for the protocol SpecView is using. You cannot have instrument using different protocols on the same comms link. If the instrument cannot be changed, then the Multiport option can be used in SpecView to talk to both protocols.
Double-check the address - maybe there are two instruments with the same address on the link, in which case they will both answer the queries from SpecView and result in corrupted comms.
Double-check baud rate and parity for all instruments, they must all be the same on the same comms link and SpecView must be setup the same also, see “Setup COM Port” inside SpecView.
|