This protocol uses the standard ModBus driver, however there is a problem related to writing to this instrument-the instrument issues busy replies to read requests for a short time after a write has occurred. This means that the ModBus driver command ECR=5 is required for all Honeywell instruments using the SpecView ModBus driver.